Protection against humidity due and rusting by complete impregnation, maximum ambient temperature 40°C, insulation class B, protection system IP 00, for installation up to IP 23, prepared for protection class II, connections for screw terminals according DGUV Vorschrift 3, separated terminals, separated winding and functional screening, midpoint for monitoring equipment of the winding, built-in PTC thermistors acc, to DIN 44081 (120°), frequency 50-60 Hz

Zeichen Suitable for medical rooms
Zeichen CE
Zeichen Approved for UK
Type: LM
Phase: 1-phase
Rated supply voltage: 230 V
Rated output voltage: 230 V
Rating: 3,15 kVA | 4,00 kVA | 5,00 kVA | 6,30 kVA | 7,00 kVA or 8,00 kVA
Design: horizontal
short-circuit voltage: < 3% of the rated input voltage
no-load current: < 3% of the rated input current
inrush current: < 12 times of the rated input current
Drawing LM Single-phase isolating transformers for the supply of medical rooms
Single-phase isolating transformer for medical rooms - type LM

Request LM Single-phase isolating transformers for the supply of medical rooms now

Are you interested in this product? Put together your desired configuration here. You can then provide further information in the inquiry form.

Product variants

Typ
type
Leistung
rating KVA
a
mm
b
mm
c
mm
d
mm
e
mm
f
mm
Gewicht
weight kg
LM 3,5 3,15 195 280 204 174 200 7,0 34,5
LM 4,5 4,00 230 340 189 204 240 9,0 40,0
LM 5,0 5,00 230 340 225 204 240 9,0 46,5
LM 6,3 6,30 260 390 220 234 280 9,0 54,0
LM 7,5 7,00 260 390 220 234 280 9,0 63,0
LM 8,8 8,00 260 390 220 234 280 9,0 77,0