Protection against humidity due and rusting by complete impregnation, maximum ambient temperature 40°C, insulation class B, protection system IP 00, for installation up to IP 23, prepared for protection class II, connections for screw terminals according to DGUV Regulation 3, separated terminals, separated windings and functional screening, midpoint for monitoring equipment of the winding, built-in thermistors (PTC) according EN 0898-1-401, frequency 50-60 Hz

Zeichen Suitable for medical rooms
Zeichen CE
Zeichen Approved for UK
Type: DLM
Phase: 3-phase
Rated supply voltage: 3 x 400 V
Rated output voltage: 3 x 230 V
Rating: 3,15 kVA | 4,00 kVA | 5,00 kVA | 6,30 kVA | 7,00 kVA | 8,00 kVA or 10,00 kVA
Design: vertical
short-circuit voltage: < 3% of the rated input voltage
no-load current: < 3% of the rated input current
inrush current: < 12 times of the rated input current
Drawing DLM Three-phase isolating transformers for the supply of medical rooms
Three-phase isolating transformer for medical rooms - type DLM

Request DLM Three-phase isolating transformers for the supply of medical rooms now

Are you interested in this product? Put together your desired configuration here. You can then provide further information in the inquiry form.

Product variants

Typ
type
Leistung
Rating KVA
a
mm
b
mm
c
mm
d
mm
e
mm
f
mm
Gewicht
weight kg
DLM 3,5 3,15 330 280 194 298 200 9,0 41,0
DLM 4,0 4,00 330 280 194 298 200 9,0 47,0
DLM 5,0 5,00 394 340 174 358 240 9,0 52,0
DLM 6,3 6,30 394 340 190 358 240 9,0 70,0
DLM 7,5 7,00 452 390 204 408 280 11,0 70,0
DLM 8,8 8,00 452 390 189 408 280 11,0 78,0
DLM 10,0 10,00 452 390 219 408 280 11,0 100,0

Other specifications are available on request. You can state your wishes and requirements in the inquiry form. Inquire now.